Determination of Proper Angle Settings for Resistance Grounded Distribution Systems for Directional Earth Fault Relays

dc.contributor.authorAtsever, Mert Bekir
dc.contributor.authorKaracasu, Ozgur
dc.contributor.authorHocaoglu, M. Hakan
dc.date.accessioned2025-10-29T11:15:51Z
dc.date.issued2020
dc.departmentGebze Teknik Üniversitesi
dc.description12th International Conference on Electrical and Electronics Engineering (ELECO) -- NOV 26-28, 2020 -- Bursa, TURKEY
dc.description.abstractThe intensive use of the underground cables in distribution systems causes the total phase-ground capacity of the system to increase. This situation causes the capacitive current based parallel tripping problem to occur frequently at the distribution system. Directional protection relays can be used to eliminate the problem and to protect the system selectively. However, it should be known selective operation of directional relays entirely depends on proper angle settings. In this study, angle setting of directional protection relays is utilise considering cable cross section, cable lenght, parallel feeders number and neutral grounding resistance. The efficiency of the selected angle adjustment methodology has been confirmed over the real distribution system.
dc.identifier.doi10.1109/ELECO51834.2020.00034
dc.identifier.endpage118
dc.identifier.isbn978-605-01-1331-0
dc.identifier.issn#DEĞER!
dc.identifier.scopus2-s2.0-85100540434
dc.identifier.scopusqualityN/A
dc.identifier.startpage113
dc.identifier.urihttps://doi.org/10.1109/ELECO51834.2020.00034
dc.identifier.urihttps://hdl.handle.net/20.500.14854/7307
dc.identifier.wosWOS:000790328900024
dc.identifier.wosqualityN/A
dc.indekslendigikaynakWeb of Science
dc.indekslendigikaynakScopus
dc.language.isotr
dc.publisherIEEE
dc.relation.ispartof2020 12th International Conference on Electrical and Electronics Engineering (Eleco)
dc.relation.publicationcategoryKonferans Öğesi - Uluslararası - Kurum Öğretim Elemanı
dc.rightsinfo:eu-repo/semantics/closedAccess
dc.snmzKA_WOS_20251020
dc.titleDetermination of Proper Angle Settings for Resistance Grounded Distribution Systems for Directional Earth Fault Relays