Mitigation of sympathy trips in highly cabled non-effectively earthed radial distribution systems via MINLP

dc.contributor.authorAtsever, Mert Bekir
dc.contributor.authorHocaoglu, Mehmet Hakan
dc.date.accessioned2025-10-29T11:27:48Z
dc.date.issued2023
dc.departmentGebze Teknik Üniversitesi
dc.description.abstractSympathy tripping problem simply refers to unnecessary operation of healthy feeder protection relays. Capacitive currents of underground cables are the main cause of sympathy tripping during the single line-to-earth faults (SLEFs) in non-effectively earthed distribution systems. Sympathy trips cause unnecessary loss of loads, increase the amount of energy-not-sold and deteriorate reliability indices. To prevent sympathy tripping in the presence of the circulating capacitive currents during the SLEF, pick-up current settings of earth fault relays should be optimized in accordance with the network topology. Accordingly, in this paper, a novel objective function and constraints have been formulated and solved using Mixed-Integer Non-linear Programming (MINLP) for optimizing the earth fault relay settings. The effectiveness of the proposed methodology has been tested by considering the effects of different cable cross-sections, fault locations, and fault resistances on a real distribution network. Therefore, with the developed MINLP approach, sympathy tripping problem is prevented. Selective protection can be provided by the optimized setting of earth fault relays in highly cabled non-effectively earthed radial distribution networks. More importantly, by using the proposed method it is possible to eliminate sympathy tripping in different radial typologies such as different numbers of parallel feeders, voltage levels, and neutral earthing structures.
dc.identifier.doi10.1016/j.epsr.2023.109377
dc.identifier.issn0378-7796
dc.identifier.issn1873-2046
dc.identifier.orcid0000-0003-2032-2261
dc.identifier.orcid0000-0001-6528-3812
dc.identifier.scopus2-s2.0-85151276549
dc.identifier.scopusqualityQ1
dc.identifier.urihttps://doi.org/10.1016/j.epsr.2023.109377
dc.identifier.urihttps://hdl.handle.net/20.500.14854/10920
dc.identifier.volume220
dc.identifier.wosWOS:000969923300001
dc.identifier.wosqualityQ2
dc.indekslendigikaynakWeb of Science
dc.indekslendigikaynakScopus
dc.language.isoen
dc.publisherElsevier Science Sa
dc.relation.ispartofElectric Power Systems Research
dc.relation.publicationcategoryMakale - Uluslararası Hakemli Dergi - Kurum Öğretim Elemanı
dc.rightsinfo:eu-repo/semantics/closedAccess
dc.snmzKA_WOS_20251020
dc.subjectEarth fault relay
dc.subjectOptimization
dc.subjectSympathy trip
dc.subjectMINLP
dc.subjectCapacitive currents
dc.titleMitigation of sympathy trips in highly cabled non-effectively earthed radial distribution systems via MINLP